37-Strand Concentric Bare And Tinned Copper Conductors

(in the English system)
Size
Conductor 
Calculated 
Approximate
Approximate 
AWG
Construction
Cross-Sectional
Conductor
Pounds per 
(Approx.)
No / inch
Area, cmils
Diameter, in.
1000 ft.
10
37/0.0159
9354
0.1113
28.88
12
37/0.0126
5874
0.0882
18.14
13
37/0.0117
5065
0.0819
15.64
14
37/0.0102
3876
0.0716
11.97
16
37/0.0080
2364
0.0560
7.30
18
37/0.0063
1468
0.0448
4.53
20
37/0.0050
926
0.0350
2.86
22
37/0.0040
596
0.0281
1.84
24
37/0.0031
357
0.0217
1.10
Applicable Specifications : ASTM B-8, B-258, B-286
Other sizes are also available on request. Please check with our sales department. 
mm = inch x 25.4
mm2 = cmils x 0.0005067
kgs / km = lbs / kft x 1.488



(in the metric system)
Size
Conductor 
Calculated 
Approximate
Approximate 
AWG
Construction
Cross-Sectional
Conductor
kgs per km
(Approx.)
No / mm
Area, mm2
Diameter, mm
@
10
37/0.404
4.7397
2.827
42.97
12
37/0.32
2.9764
2.240
26.99
13
37/0.297
2.5664
2.080
23.27
14
37/0.26
1.9640
1.819
17.81
16
37/0.203
1.1978
1.422
10.86
18
37/0.16
0.7438
1.138
6.74
20
37/0.127
0.4692
0.889
4.26
22
37/0.102
0.3020
0.714
2.74
24
37/0.079
0.1809
0.551
1.64

         

(c) copyright2001 TAIFINI COPPER & CONDUCTOR INC. All Rights Reserved.